GL 308 i GL 309
Rated voltage 52/72.5 kV
Rated frequency 50/60 Hz
Rated normal current up to 2000 A
Rated short-circuit breaking current up to 31.5/25 kA
Rated short-circuit making current 80/65 kA
Reliable performance thanks to field-proven components and rigorous testing
Streamlined installation and commissioning thanks to full assembly before shipping
Long service intervals
GE’s GL 308/309 live tank circuit breakers for overhead installations are equipped with third-generation self-exhaust switching chambers and spring actuators. The reliable connection chamber works on the principle of energy-optimized self-exhaust. Live tank circuit breakers provide customers with a high level of reliability, even in extremely difficult conditions and climates or in areas with high seismic activity.
The switches are pre-adjusted, filled with SF6 and fully assembled at the factory before shipment. Thanks to this pre-assembly, no adjustments are necessary during installation and commissioning of the circuit breaker, allowing for quick and easy on-site installation with long maintenance intervals. Moreover, the switching compartment of the circuit breaker can be independently dismantled without dismantling the entire pole column.
GE live tank circuit breakers have met the requirements of national and international standards. This has been confirmed by comprehensive testing based on the latest IEC standards.
The entire development and production procedures of our live tank circuit breakers are fully compliant with the latest quality standards ISO 9001, ISO 14001 and OHSAS 18001. This ensures the high quality of our products and services, which is confirmed by regular audits.
Technical data GL 308 and GL 309